Thermia iTec is an air source heat pump with inverter technology.
The inverter-controlled compressor adjusts the heat load constantly
according to the current heat demand. You never use more energy
than is needed, and this of course reduces your energy bills further.
Energy is collected from the outdoor air, and is used to heating of
hot water and hydronic heating systems, delivering efficient energy
savings at temperatures as low as -25 °C. By a unique acoustic
design, it is very quiet in operation. The cooling function assures
a pleasant indoor climate also during the hottest period of the year.
And if you have a swimming pool, you can reduce the heating cost
significantly as Thermia iTec is prepared for heating of pools.
With a high seasonal performance Thermia iTec allows you to reduce
your energy consumption by up to 75%.
Thermia iTec is available in three output sizes: 5 kW, 9 kW
and 16 kW. It consists of two parts: the heat pump itself, which is
installed outdoors, and an indoor unit. You can choose from four
versions of the indoor unit, each with different features. The choice
of unit depends on the set-up of your heating system, to ensure you
never pay for more than you actually need. With Thermia Online you
have the ability to remotely control and monitor your heat pump.
iTec | 1~230 V, 50 Hz | 3~400 V, 50 Hz | |||||
5 | 9 | 16 | 9 | 16 | |||
Refrigerant | Type | R410A | R410A | R410A | R410A | R410A | |
Amount 10 | kg | 1.15 | 1.4 | 2.6 | 1.5 | 2.6 | |
Test pressure | MPa | 12.3 | 12.3 | 12.3 | 12.3 | 12.3 | |
Design pressure | MPa | 4.1 | 4.1 | 4.1 | 4.1 | 4.1 | |
Compressor | Type | BLDC Twin Rotary | BLDC Twin Rotary | BLDC Twin Rotary | BLDC Twin Rotary | BLDC Twin Rotary | |
Oil | POE | POE | PVE | PVE | PVE | ||
Electrical data | Main supply | Volt | 230 | 230 | 230 | 400 | 400 |
Rated power, cooling | kW | 1,21 | 1,95 | 3,84 | 1,92 | 3,84 | |
Rated power, heating | kW | 1,67 | 2,20 | 3,75 | 2,20 | 3,75 | |
Fuse | A | 16 | 16 | 32 | 10 | 16 | |
Performance | COP 1 | 4.72 | 4.21 | 4.21 | 4.21 | 4.21 | |
Heating capacity 1 | kW | 5.0 | 9.0 | 16.0 | 9.0 | 16.0 | |
Power input – heating 1 | kW | 1.06 | 2.14 | 3.8 | 2.14 | 3.8 | |
EER 2 | 4.13 | 3.85 | 3.65 | 3.65 | 3.65 | ||
Cooling capacity 2 | 5.0 | 7.5 | 14.0 | 7.0 | 14.0 | ||
Power input – cooling 2 | 1.21 | 1.95 | 3.84 | 1.92 | 3.84 | ||
SCOP 14825 (Average climate) Low temp | 4.56 | 4.39 | 4.41 | 4.47 | 4.41 | ||
SCOP 14825 (Cold climate) Low temp | 3.78 | 3.99 | 3.90 | 3.97 | 3.90 | ||
SCOP 14825 (Average climate) High temp | 3.19 | 3.19 | 2.82 | 3.26 | 2.82 | ||
SCOP 14825 (Cold climate) High temp | 2.54 | 2.88 | 2.74 | 2.73 | 2.74 | ||
Energy class – system 8 | Floor heating (35°C)/Radiator (55°C) | A+++/A++ | A+++/A++ | A+++/A+ | A+++/A++ | A+++/A+ | |
Energy class – product 9 | Floor heating (35°C)/Radiator (55°C) Domestic hot water / Declared load profile | A+++/A++ A+/L | A++/A++
A/L |
A++/A+
A/L |
A+++/A++
A/L |
A++/A+
A/L |
|
Nominal flow 3 | Heating circuit | l/s | 0.24 | 0.43 | 0.76 | 0.36 | 0.67 |
Operating range (outdoor) | Heating | °C | -25~+35 | -25~+35 | -25~+35 | -25~+35 | -25~+35 |
Cooling | °C | +10~+46 | +10~+46 | +10~+46 | +10~+46 | +10~+46 | |
Domestic hot water | °C | -25~+43 | -25~+43 | -25~+43 | -25~+43 | -25~+43 | |
Max temperature 4 | Heating circuit | °C | 55 | 55 | 55 | 55 | 55 |
Sound power level | Regular mode 5 | dB(A) | 61 | 63 | 66 | 63 | 66 |
Sound pressure level | 1m 6 | dB(A) | 46 | 48 | 51 | 48 | 51 |
4m 7 | dB(A) | 44 | 46 | 49 | 46 | 49 | |
Weight | Outdoor unit | kg | 59 | 76 | 108 | 76 | 108 |
Standard | kg | 18 | 18 | 18 | 18 | 18 | |
Plus | kg | 21 | 21 | 21 | 21 | 21 | |
Total | kg | 106 | 106 | 106 | 106 | 106 | |
Total +60 | kg | 142 | 142 | 142 | 142 | 142 | |
Total Compact | kg | 100 | 100 | 100 | 100 | 100 | |
Dimensions (WxDxH) | Outdoor unit | mm | 880 x 310 x 798 | 940 x 330 x 998 | 940 x 330 x 1420 | 940 x 330 x 998 | 940 x 330 x 1420 |